The SpectrAlert Advance wall-mount horn strobe is rich with features guaranteed to delive cost-efficient installation time. Features include universal mounting plate with plug-in design, 11 field-selectable candela settings, dual voltage in one product, and rotary switches to select horn tone and volume settings. SpectrAlert Advance horn strobes are listed to UL 1971 and UL 464. Model numbers with a “K” suffix are listed to UL 1638 and NEMA 4X for outdoor use.
* For all SpectrAlert Advance models, a -P suffix denotes plain housing (no “FIRE” print); -SP denotes “FUEGO” -printed housing. Outdoor units with model numbers ending with -R do not include weatherproof back boxes, especially for use with WTP models for flush mounting outdoor devices. Outdoor units with model numbers ending in K do include weatherproof back boxes.
Description
UL Max. Strobe Current Draw (mA RMS)
To calculate current draw for 4-wire horn strobes, add the required strobe current and horn current from the tables below:
Standard Candela
Red Model Number: P4R | Outdoor P4RK P4RK-R
White Model Number: P4W | Outdoor P4WK
Candela- 15
8-17.5 Volts
DC- 123
FWR- 128
16-33 Volts
DC- 66
FWR- 71
Candela- 15/75
8-17.5 Volts
DC- 142
FWR- 148
16-33 Volts
DC- 77
FWR- 81
Candela- 30
16-33 Volts
DC- 94
FWR- 96
Candela- 75
16-33 Volts
DC- 158
FWR- 153
Candela- 95
16-33 Volts
DC- 181
FWR-176
Candela- 110
16-33 Volts
DC- 202
FWR- 195
Candela- 115
16-33 Volts
DC- 210
FWR- 205
High Candela
Red Model Number: P4RH |
White Model Number: Outdoor: P4WHK
Candela- 135
16-33 Volts
DC- 228
FWR- 207
Candela- 150
16-33 Volts
DC- 246
FWR- 220
Candela- 177
16-33 Volts
DC- 281
FWR- 251
Candela- 185
16-33 Volts
DC- 286
FWR- 258
UL Max. Horn Current Draw (mA RMS)
Sound Pattern- Temporal
dB- High
8-17.5 Volts
DC- 57
FWR- 55
16-33 Volts
DC- 69
FWR- 75
Sound Pattern- Temporal
dB- Medium
8-17.5 Volts
DC- 44
FWR- 49
16-33 Volts
DC- 69
FWR- 69
Sound Pattern- Temporal
dB- Low
8-17.5 Volts
DC- 38
FWR- 44
16-33 Volts
DC- 44
FWR- 48
Sound Pattern- Non Temporal
dB- High
8-17.5 Volts
DC- 57
FWR- 56
16-33 Volts
DC- 69
FWR- 75
Sound Pattern- Non Temporal
dB- Medium
8-17.5 Volts
DC- 42
FWR- 50
16-33 Volts
DC- 60
FWR- 69
Sound Pattern- Non Temporal
dB- Low
8-17.5 Volts
DC- 41
FWR- 44
16-33 Volts
DC- 50
FWR- 50
Sound Pattern- Coded
dB-High
8-17.5 Volts
DC- 57
FWR- 55
16-33 Volts
DC- 69
FWR- 75
Sound Pattern- Coded
dB- Medium
8-17.5 Volts
DC- 44
FWR- 51
16-33 Volts
DC- 56
FWR- 69
Sound Pattern-Coded
dB- Low
8-17.5 Volts
DC- 40
FWR- 46
16-33 Volts
DC- 52
FWR- 50