The T-Tap water flow detectors are compatible with one-inch NPT-style connections, making them ideal for residential or branch line signaling applications.
Description
Model – WFDTN
Compatible Tee Fittings – 1′′ to 11 /2′′ NPT threaded ferrous and brass, 1′′ to 2′′ sweat brass, 11/2′′ polybutylene plastic, 1′′ PVC plastic tees having a 1′′ threaded NPT branch, and 2′′ cast and malleable threaded tees.
Pressure Rating – 250 psi
Contact Ratings – 2 Form C: 10 A @ 125/250 VAC, 2.5 A 24 VDC
Triggering Threshold – 4-10 gpm
Model – WFDTH
Compatible Tee Fittings – 1′′ to 11 /2′′ NPT threaded ferrous and brass, 1′′ to 2′′ sweat brass, 11/2′′ polybutylene plastic, 1′′ PVC plastic tees having a 1′′ threaded NPT branch, and 2′′ cast and malleable threaded tees.
Pressure Rating – 250 psi
Contact Ratings – 2 Form C: 10 A @ 125/250 VAC, 2.5 A 24 VDC
Triggering Threshold – 4-10 gpm
Model – WFDTNR
Compatible Tee Fittings – 1′′ to 11 /2′′ NPT threaded ferrous and brass, 1′′ to 2′′ sweat brass, 11/2′′ polybutylene plastic, 1′′ PVC plastic tees having a 1′′ threaded NPT branch, and 2′′ cast and malleable threaded tees.
Pressure Rating – 250 psi
Contact Ratings – 2 Form C: 10 A @ 125/250 VAC, 2.5 A 24 VDC
Triggering Threshold – 4-10 gpm
Model – WFDNFS
Compatible Tee Fittings – 1′′ to 2″ CPVC tees
Pressure Rating – 175 psi
Contact Ratings – 2 sets of SPDT Form C: 10 A @ 125/250 VAC, 2.5 @ 6/12/24 VDC
Triggering Threshold – 4-10 gpm
Model – WFDNFT
Compatible Tee Fittings – 1′′ to 2′′ CPVC tees, 1″ to 2″ brass threaded tees, 1″ to 2″ copper sweat tees
Pressure Rating – 175 psi
Contact Ratings – 2 sets of SPDT Form C: 10 A @ 125/250 VAC, 2.5 @ 6/12/24 VDC
Triggering Threshold – 4-10 gpm